Treat symptom-based questions as structured diagnosis exercises. The safest method is usually the correct method.
Japanese Key Term
保守点検(ほしゅてんけん / maintenance inspection)
Hiragana
ほしゅてんけん
English Meaning
Maintenance inspection
Simple Explanation
Many written questions describe symptoms. You need to identify likely cause, risk, and first safe action.
Detailed Explanation
Fault-based questions often mention smell, intermittent operation, breaker trips, visible insulation damage, or unusual heating. Link each symptom to a likely mechanism: contact resistance, overcurrent, leakage, or insulation breakdown. Then choose actions that prioritize safety: isolate, verify, inspect, and test before restoration. This structure aligns with both exam logic and real electrical practice.
Key Vocabulary
- 保守点検(ほしゅてんけん / maintenance inspection)
- 接触不良(せっしょくふりょう / poor contact)
- 絶縁抵抗(ぜつえんていこう / insulation resistance)
- 地絡(ちらく / ground fault)
Formula
Decision sequence: symptom -> likely fault mechanism -> safety-first action -> confirm by test.
Worked Example
Repeated leakage trips after rain may indicate moisture-related insulation deterioration. First action is safe isolation and testing, not repeated breaker reset.
Exam Tips
Answers that prioritize immediate re-energization without verification are usually wrong in safety-focused prompts.
Common Exam Trap
Confusing symptom relief with root-cause correction. A reset is not a repair.
Site Reality in Japan
Accurate diagnosis prevents repeat faults and protects people, property, and schedule.
Practice Question
A circuit trips intermittently and terminals show discoloration. What fault mechanism is most likely?
Answer
Poor contact causing local heating and unstable operation
Explanation
Discoloration often indicates heat from resistance at a bad connection. Investigation and correction are required before re-energizing.
1. Two 30 ohm resistors are in series. What is total resistance?
Series resistance adds directly.
2. Two 30 ohm resistors are in parallel. What is total resistance?
Equal parallel resistors halve the value.
3. A bad joint has 0.5 ohms resistance. If 10 A flows, power loss at the joint is:
P = I^2 R = 100 x 0.5 = 50 W.
4. What is the meaning of 力率?
力率 means power factor.
5. In a series AC circuit, if total voltage is 100 V and resistor voltage is 80 V, the power factor is closest to:
cos(phi) = Vr / V = 80 / 100.
6. Which notation means single-phase three-wire?
1phi3W is single-phase three-wire.